DDC Field Controller

DLI-16.0.0.0

DLI-16.0.0.0 is a simple, stable and high-performance input/output device with standard open protocols. It supports independent communication to meet general and special applications and features two open communication protocols: Bacnet MS/TP and Modbus RTU. DLI-16.0.0.0 can control and manage remote controlled devices via field bus connections to satisfy general and special applications. It can be used either as a simple I/O monitoring module or as a field controller with specific functions.

Function Overview
  • Multi-protocol DDC controller, supporting BACnet MS/TP and Modbus protocols via RS-485
  • Compatible with various BA and industrial control software systems, multiple I/O types
  • 16 input channels for isolated digital input
  • Modular programming, WYSIWYG
  • Built-in multiple commonly used application algorithms
Specifications

Electrical Parameters

● Power Supply

24VAC 50/60Hz ±5%, or 24VDC~34VDC

● Power Consumption

<11VA

● Auxiliary Output Power

24Vdc Max: 200mA

● Operating Temperature

0 ~ 50℃

● Storage Temperature

-10 ~ 60℃

● Operating Humidity

5%~95% non-condensing

● Battery

CR2032 coin cell battery

Communication Parameters

Interface 1

EIA-485 standard communication interface, half-duplex, multi-drop line

● Baud Rate

9.6K, 19.2k, 38.4K, 76.8K bps

● Data Bits

8 bits

● Parity

None, Even, Odd

● Application Protocol

Modbus RTU / BACnet MS/TP

I/O Configuration

Digital Input

16 channels

● Type

Dry contact (Limit: +5V at 500 Ohm Resistance maximum)

Other Parameters

● CPU

Cortex 128MHz Processor

● Dimensions

158mm*110mm*60mm

● Material

Flame-retardant engineering plastic

● Weight

180g

 