DDC Field Controller

DLI-5.4.8.2

supports independent communication and can meet general and special applications. It comes with two open communication protocols: Bacnet MSTP and Modbus RTU. DLI-5.4.8.2 can control and manage remote controlled devices via field bus connections to satisfy general and special applications. It can be used either as a simple I/O monitoring module or as a field controller with specific functions.

Function Overview
  • Multi-protocol DDC controller, supporting BACnet MS/TP and Modbus protocols via RS-485;
  • Standard protocols, compatible with various configuration software;
  • 8 input channels configurable for voltage input, current input, digital input, resistance measurement and NTC10K input measurement;
  • 5 input channels for isolated digital input;
  • 2 output channels configurable for voltage output, current output and digital output (for external relay control);
  • 4 output channels with relay output;
  • 8 input channels adopt high-speed 12-bit A/D sampling for analog input signals;
  • 2 output channels adopt high-speed 16-bit D/A conversion to generate analog output signals;
  • Modular programming, WYSIWYG;
  • Built-in multiple commonly used application algorithms
Specifications

Electrical Parameters

Power Supply

24VAC 50/60Hz ±5%, or 24VDC~34VDC

Power Consumption

<11VA

Auxiliary Output Power

Output power for external sensors: 24Vdc Max:200mA

Operating Temperature

0 ~ 50℃

Storage Temperature

-10 ~ 60℃

Operating Humidity

5%~95% non-condensing

Communication Parameters

Interface 1

EIA-485 standard communication interface, half-duplex, multi-drop line

Baud Rate

9.6K, 19.2k, 38.4K, 76.8K bps

Data Bits

8 bits

Parity

None, Even, Odd

Application Protocol

Modbus RTU, Bacnet MS/TP

Interface 2

EIA-485 standard communication interface, half-duplex, multi-drop line

Baud Rate

9.6K, 19.2k, 38.4K bps

Data Bits

8 bits

Parity

None, Even, Odd

Application Protocol

Modbus RTU

I/O Configuration

Universal Input

8 channels

Voltage

0-10V(±0.0005V), 0-5V(±0.0003V)

Current

0-20mA(±0.01mA), 4-20mA(±0.01mA)

Resistance

0 - 30K(±10 Ohm), 0 - 10K(±5 Ohm)

Thermistor

NTC10K

Switch

Dry contact (Limit: +5V at 500 Ohm Resistance maximum)

Digital Input

5 channels

Type

Dry contact (Limit: +5V at 500 Ohm Resistance maximum)

Universal Output

2 channels

Voltage

0-10V

Current

0-20mA, 4-20mA(up to 800 Ohm load)

Switch

External 24VDC relay output (50mA max, built-in power supply)

Digital Output

4 channels

Type

Relay, SPST NO, 30VDC 5A    250VAC 5A

Other Parameters

CPU

Cortex 128MHz Processor

Dimensions

204mm*143mm*54mm

Material

Flame-retardant engineering plastic

Weight

300g

 